3RA2711-1CA00
SIRIUS NG CONNECT

From SIEMENS

Function module for IO-Link, star-delta (wye-delta) start, screw terminal, Installation on contactors 3RT2 Communication-capable contactor required
General technical data:
Product brand nameSirius
Product designationfunction module
Design of the productIO-Link
Size of contactor can be combined company-specificS00, S0, S2, S3
Protection class IP on the frontIP20
Degree of pollution3
Insulation voltage with degree of pollution 3 rated valueV690
Installation altitude at height above sea level maximumm2 000
Ambient temperature
during storage°C-40 ... +80
during operation°C-25 ... +60
during transport°C-40 ... +80
EMI immunity acc. to IEC 60947-1ambience A (industrial sector)
EMC emitted interference acc. to IEC 60947-1CISPR11, ambience A (industrial sector)
Conducted interference due to burst acc. to IEC 61000-4-42 kV network connection / 1 kV control connection
Conducted interference due to conductor-earth surge acc. to IEC 61000-4-51 kV
Conducted interference due to conductor-conductor surge acc. to IEC 61000-4-50.5 kV
Electrostatic discharge acc. to IEC 61000-4-28 kV
Field-bound parasitic coupling acc. to IEC 61000-4-310 V/m
Shock resistance11g / 15 ms
Vibration resistance10 ... 55 Hz / 0.35 mm
Reference indentifier acc. to DIN 40719 extended according to IEC 204-2 acc. to IEC 750K
Reference identifier acc. to DIN EN 61346-2K
Suitability for use
direct starterNo
star-delta starterYes
reversing starterNo
Communication/ Protocol:
Product function
Bus communicationYes
Control circuit interface with IO linkYes
Control circuit interface with AS interfaceNo
Control circuit/ Control:
Design of the surge suppressorVaristor
Type of voltage of the control supply voltageDC
Control supply voltage 1 at DC rated valueV24
Installation/ mounting/ dimensions:
Mounting positionany
Mounting typecan be plugged into contactor
Widthmm45
Heightmm37
Depthmm75
Connections/ Terminals:
Product function removable terminal for auxiliary and control circuitYes
Type of electrical connection for auxiliary and control current circuitscrew-type terminals
Type of connectable conductor cross-sections
for auxiliary contacts
— solid0.5 ... 4 mm², 2x (0.5 ... 2.5 mm²)
— finely stranded
— with core end processing1x (0.5 ... 2.5 mm²), 2x (0.5 ... 1.5 mm²)
at AWG conductors for auxiliary contacts2x (20 ... 14)

External links