Power regulator Current range 20 A / 40 °C 400-600 V / 24 V AC/DC for semiconductor relay / contactor
General technical data
Product brand nameSIRIUS
Product designationpower regulator
Product functionsolid-state relay / solid-state contactor 3RF2
Number of poles for main current circuit0
Protection class IPIP20
Product designation _1 of the accessories that can be orderedsealable end cover
Manufacturer's article number _1 of the accessories that can be ordered
Product designation _2 of the accessories that can be orderedinput reactor / 1AC
Manufacturer's article number _2 of the accessories that can be ordered
Hole diameter of the current transformermm17
Ambient temperature
during operation°C-25 ... +60
during storage°C-55 ... +80
Installation altitude at height above sea level maximumm1 000
Vibration resistance acc. to IEC 60068-2-62g
Shock resistance acc. to IEC 60068-2-2715g / 11 ms
Reference code acc. to DIN 40719 extended according to IEC 204-2 acc. to IEC 750A
Reference code acc. to DIN EN 61346-2K
Main circuit
Number of NO contacts for main contacts0
Number of NC contacts for main contacts0
Operating current
at AC-1 at 400 V rated valueA20
Derating temperature°C40
Operating voltage at AC
at 50 Hz rated valueV400 ... 600
at 60 Hz rated valueV400 ... 600
Operating range relative to the operating voltage at AC
at 50 HzV340 ... 660
at 60 HzV340 ... 660
Operating frequency rated valueHz50 ... 60
Relative symmetrical tolerance of the operating frequency%10
Insulation voltage rated valueV600
Compensation of the supply voltage fluctuations%20
Teach range currentA4 ... 20
Current measuring rangeA0 ... 22
Control circuit/ Control
Type of voltageAC/DC
Control supply voltage
at DC
— rated valueV18 ... 30
— Full-scale value for signal<0> recognitionV5
at AC
— at 50 Hz
— rated valueV20.5 ... 26.5
— Full-scale value for signal<0> recognitionV5
— at 60 Hz
— rated valueV20.5 ... 26.5
— Full-scale value for signal<0> recognitionV5
Supply voltage frequency for auxiliary and control current circuit rated valueHz50 ... 60
Symmetrical line frequency toleranceHz5
Relative symmetrical tolerance of the supply voltage frequency%10
Control current
at AC rated valuemA40
at DC rated valuemA40
Operating voltage at the analog inputV-1 ... +11
Source resistance at the analog input8 000
Auxiliary circuit
Number of NC contacts for auxiliary contacts1
Number of NO contacts for auxiliary contacts0
Number of CO contacts for auxiliary contacts0
Operating voltage of auxiliary contacts
at ACV15 ... 30
at DCV15 ... 30
Operating current of auxiliary contacts
at ACmA5 ... 1 000
at DCmA5 ... 1 000
Installation/ mounting/ dimensions
Mounting typeclip-on
Mounting type Side-by-side mountingYes
Widthmm45
Heightmm111.5
Depthmm69.5
Connections/Terminals
Type of electrical connection
for auxiliary and control current circuitscrew-type terminals
Design of the thread of the connection screw of the auxiliary and control contactsM3
Type of connectable conductor cross-sections
for auxiliary and control contacts
— solid1x (0.5 ... 2.5 mm²), 2x (0.5 ... 1.0 mm²)
— finely stranded
— with core end processing1x (0.5 ... 2.5 mm²), 2x (0.5 ... 1.0 mm²)
— without core end processing1x (0.5 ... 2.5 mm²), 2x (0.5 ... 1.0 mm²)
at AWG conductors for auxiliary and control contacts1x (AWG 20 ... 12)
Connectable conductor cross-section for auxiliary and control contacts
solidmm²0.5 ... 2.5
finely stranded
— with core end processingmm²0.5 ... 2.5
— without core end processingmm²0.5 ... 2.5
AWG number as coded connectable conductor cross section for auxiliary and control contacts12 ... 20
Wire stripping length of the cable for auxiliary and control contactsmm7