3RK3111-2AA10
MSS 3RK3, CENTRAL MODULE BASIC

From SIEMENS

SIRIUS, central unit 3RK3 Basic for modular Safety system 3RK3 4/8 F-DI,1F-RO,1 F-DO,24 V DC parameterizable using software Safety ES 45 mm overall width Spring-type terminal Up to SIL3 (IEC 61508) Up to Performance Level E (ISO 13849-1)
Product brand nameSIRIUS
Product categoryModular Safety System
Product designationCentral unit
General technical data
Product function
EMERGENCY STOP functionYes
protective door monitoringYes
protective door monitoring with tumblerNo
muting, 2 sensor-parallelNo
muting, 4 sensor-parallelNo
muting, 4 sensor-sequentialNo
Monitoring parameterizableNo
evaluation: electro-sensitive protective equipmentYes
evaluation: selector switchYes
Pressure-sensitive mat monitoringYes
evaluation: two-hand operator panelYes
evaluation: enabling switchYes
monitored start-upYes
two-hand control acc. to EN 574Yes
Number of function blocks typical300
Insulation voltage rated value300 V
Degree of pollution3
Surge voltage resistance rated value2 500 V
Consumed current for rated value of supply voltage1.685 A
Protection class IPIP20
of the enclosureIP20
of the terminalIP20
Shock resistance15g / 11 ms
Vibration resistance acc. to IEC 60068-2-65 ... 500 Hz: 0.75 mm
Operating frequency maximum1 000 1/h
Mechanical service life (switching cycles) typical10 000 000
Product function suitable for AS-i Power24VNo
Product function Diagnostics with CTT2 slaveNo
Protocol is supported ASIsafe (Safety at work) protocolNo
Suitability for use
Monitoring of floating sensorsYes
Monitoring of non-floating sensorsYes
position switch monitoringYes
EMERGENCY-OFF circuit monitoringYes
valve monitoringYes
opto-electronic protection device monitoringYes
proximity switch monitoringYes
safety-related circuitsYes
Suitability for use for monitoring of optoelectronic protective devices acc. to IEC 61496-1Yes
Operating power rated value4.5 W
Communication/ Protocol
Protocol optional is supported PROFIBUS DP protocolYes; when using the DP interface module; 32 bit cyclical data
Protocol is supported AS-interface protocolNo
Amount of data of the cyclic user data
for inputs with PROFIBUS DP32 bit
for outputs with PROFIBUS DP32 bit
Control circuit/ Control
Type of voltageDC
Type of voltage of the control supply voltageDC
Control supply voltage rated value24 V
Control supply voltage 1 at DC rated value24 V
Inrush current peak
at 24 V70 A
Duration of inrush current peak
at 24 V1 ms
Consumed current for rated value of supply voltage without semiconductor output185 mA
Inputs/ Outputs
Product function
Parameterizable inputsYes
Parameterizable outputsYes
Number of inputs
safety-related8
non-safety-related0
Input delay time0 ... 150 ms
Number of outputs
safety-related 2-channel2
for testing contact-based sensors2
Number of outputs as contact-affected switching element safety-related
1-channel0
2-channel1
Number of outputs as contact-less semiconductor switching element
safety-related 2-channel1
non-safety-related 2-channel0
Pulse duration of the contactless semiconductor contact block for switching off safety-related maximum1 ms
Recovery time of the safe outputs420 ms
Switching capacity current of semiconductor outputs at DC-13 at 24 V1.5 A
Installation/ mounting/ dimensions
Mounting positionvertical
Mounting typeSnap-mounted to DIN rail or screw-mounted with additional push-in lug
Height113 mm
Width45 mm
Depth124 mm
Connections/Terminals
Product function
removable terminalYes
removable terminal for control circuitYes
removable terminal for auxiliary and control circuitYes
Type of electrical connectionspring-loaded terminals
for auxiliary and control current circuitspring-loaded terminals
Type of connectable conductor cross-sections
solid2x (0.25 ... 1.5 mm²)
finely stranded with core end processing2x (0.25 ... 1 mm²)
at AWG conductors solid2x (24 ... 16)
at AWG conductors stranded2x (24 ... 16)
Connectable conductor cross-section finely stranded with core end processing0.25 ... 1.5 mm²
AWG number as coded connectable conductor cross section
solid24 ... 16
stranded24 ... 16
DC resistance of the cable maximum100 Ω
Safety related data
Safety Integrity Level (SIL) acc. to IEC 61508SIL CL 3
SIL Claim Limit (subsystem) acc. to EN 62061Kat. 4 / SIL3 / Ple
Performance level (PL) acc. to EN ISO 13849-1e
Category acc. to EN ISO 13849-14
Stop category acc. to DIN EN 60204-10 / 1
PFHD with high demand rate acc. to EN 620610.0000000051 1/h
Hardware fault tolerance acc. to IEC 615081
T1 value for proof test interval or service life acc. to IEC 6150820 y
Protection against electrical shockfinger-safe
Category acc. to EN 954-14
Short-circuit protection
Design of the fuse link for short-circuit protection of the NO contacts of the relay outputs requiredNH Type 3NA, DIAZED Type 5SB, NEOZED Type 5SE
Electromagnetic compatibility
Installation environment regarding EMCThis product is suitable for Class A environments only. It can cause undesired radio-frequency interference in residential environments. If this is the case, the user must take appropriate measures.
Conducted interference
due to burst acc. to IEC 61000-4-42 kV (power ports) / 1 kV (signal ports)
due to conductor-earth surge acc. to IEC 61000-4-52 kV
due to conductor-conductor surge acc. to IEC 61000-4-51 kV
Field-bound parasitic coupling acc. to IEC 61000-4-310 V/m
Electrostatic discharge acc. to IEC 61000-4-24 kV contact discharge / 8 kV air discharge
Ambient conditions
Installation altitude at height above sea level maximum2 000 m
Ambient temperature
during operation-20 ... +60 °C
during storage-40 ... +85 °C
during transport-40 ... +85 °C
Air pressure acc. to SN 3120570 ... 106 kPa