4AT4502-5MT10-0CM4
STTRAF PN PN(S6)16 80,8KVA UPRI480+ -5%V

From SIEMENS

CONTROL CIRCUIT TRANSFORMER; PHASES:1; PN/PN(S6)(KVA):16 /82,529; UPRI(V):690+/-5%; USEC(V):230; ISEC(A):69,6; F(HZ):50...60; VECTOR GR./SHIELD WNG.:II0 /0; TA/ISOKL:55 /H; IP00; TYPE OF TERMINALS:SCREW CONNECTION; INSTALLATION:SCREW; EN 61558-2-1, -2-2, -2-4 >CONTROL CIRCUIT TRANSFORMER< >ISOLATION TRANSFORMER<
General technical data:
Product designationcontrol circuit transformer
Product brand nameSIDAC
Operating apparent output rated valueV·A16 000
Efficiency0.96
Connection method for transformersIi0
Certificate of suitabilityCE
Product function
Temperature monitoringYes
Insulation monitoringNo
Short-circuit and overload proofNo
Number of shielding windings0
Short-term vector powerV·A82 500
Relative short-circuit voltage%2.6
Inputs:
Phase number of the inputs1
Input voltage
_1 rated valueV725
_2 rated valueV690
_3 rated valueV655
Electrical input frequency
minimumHz50
maximumHz60
Outputs:
Phase number of the outputs1
Output voltage
_1 rated valueV230
Electrical output frequency
maximumHz60
minimumHz50
Ambient conditions:
Thermal class acc. to IEC 60085H
Ambient temperature rated value°C55
Protection class IPIP00
Mechanical data:
Type of electrical connection
at output for main current circuitscrew-type terminals
at input for main current circuitscrew-type terminals
Type of the temperature monitoringwarning
Mounting typescrews
Construction form of the iron coreUI 240/107
Widthm0.256
Heightm0.42
Depthm0.221

External links