6AG1132-4BF00-7AA0
SIPLUS ET200S EM 8 DO

From SIEMENS

SIPLUS ET 200S EM 8 DO -25...+70°C with conformal coating based on 6ES7132-4BF00-0AA0 . Electronics module for ET 200S, 8 DO 24 V DC/0.5A 15 mm width, 1 unit per packing unit
Supply voltage
Reverse voltage protectionYes
Load voltage L+
Rated value (DC)24 V
Reverse polarity protectionYes
Input current
from load voltage L+ (without load), max.5 mA; Per channel
from backplane bus 3.3 V DC, max.10 mA
Power loss
Power loss, typ.1.5 W
Address area
Address space per module
Address space per module, max.1 byte
Digital outputs
Number of digital outputs8
Short-circuit protectionYes
Response threshold, typ.1.5 A
Limitation of inductive shutdown voltage toTyp. L+ (-55 to -60 V)
Controlling a digital inputYes
Switching capacity of the outputs
on lamp load, max.5 W
Load resistance range
lower limit48 Ω
upper limit3 400 Ω
Output voltage
for signal "1", min.L+ (-1.0 V)
Output current
for signal "1" rated value0.5 A
for signal "1" permissible range, min.7 mA
for signal "1" permissible range, max.600 mA
for signal "0" residual current, max.0.3 mA
Output delay with resistive load
"0" to "1", max.300 µs
"1" to "0", max.600 µs
Parallel switching of two outputs
for upratingNo
for redundant control of a loadYes
Switching frequency
with resistive load, max.100 Hz
with inductive load, max.2 Hz
on lamp load, max.10 Hz
Total current of the outputs
Current per module, max.4 A
Cable length
shielded, max.1 000 m
unshielded, max.600 m
Isochronous mode
Isochronous operation (application synchronized up to terminal)Yes; jitter incumbered < 100us
Interrupts/diagnostics/status information
Diagnostics functionNo
Diagnostics indication LED
Status indicator digital output (green)Yes
Parameter
Remark3-byte parameter (not accessible for the user)
Potential separation
Potential separation digital outputs
between the channelsNo
between the channels and backplane busYes
Isolation
Isolation tested with500 V DC
Ambient conditions
Ambient temperature during operation
min.-40 °C; = Tmin
max.70 °C; = Tmax
Altitude during operation relating to sea level
Installation altitude above sea level, max.5 000 m
Ambient air temperature-barometric pressure-altitudeTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)
Relative humidity
With condensation, tested in accordance with IEC 60068-2-38, max.100 %; RH incl. condensation/frost (no commissioning under condensation conditions)
Resistance
Use in stationary industrial systems
— to biologically active substances according to EN 60721-3-3Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request
— to chemically active substances according to EN 60721-3-3Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-3Yes; Class 3S4 incl. sand, dust, *
Use on ships/at sea
— to biologically active substances according to EN 60721-3-6Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on request
— to chemically active substances according to EN 60721-3-6Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-6Yes; Class 6S3 incl. sand, dust; *
Remark
— Note regarding classification of environmental conditions acc. to EN 60721* The supplied plug covers must remain in place over the unused interfaces during operation!
Dimensions
Width15 mm
Height81 mm
Depth52 mm
Weights
Weight, approx.40 g
last modified:03/25/2019