| SIPLUS ET 200S EM 2RO 24 V DC-230 V AC/5 A -25...+70°C based on 6ES7132-4HB01-0AB0 5 units per packing unit . 5 electronic modules for ET 200S, 2 DO relay 24 V DC-230 V AC/5 A, 15 mm width, Substitute value output with LED SF (group fault) |
Supply voltage |
Load voltage L+ |
Rated value (DC) | 24 V; From power module |
Reverse polarity protection | Yes |
Input current |
from load voltage L+ (without load), max. | 30 mA |
from backplane bus 3.3 V DC, max. | 10 mA |
Power loss |
Power loss, typ. | 0.6 W |
Address area |
Address space per module |
Address space per module, max. | 1 byte |
with packing | 2 bit |
Digital outputs |
Number of digital outputs | 2 |
Short-circuit protection | No |
Limitation of inductive shutdown voltage to | No |
Controlling a digital input | Yes |
Output current |
for signal "1" rated value | 5 A |
for signal "1" minimum load current | 8 mA |
Parallel switching of two outputs |
for uprating | No |
for redundant control of a load | No |
Switching frequency |
with resistive load, max. | 2 Hz |
with inductive load, max. | 0.5 Hz |
on lamp load, max. | 2 Hz |
Relay outputs |
Switching capacity of contacts |
— Thermal continuous current, max. | 5 A |
Cable length |
shielded, max. | 1 000 m |
unshielded, max. | 600 m |
Isochronous mode |
Isochronous operation (application synchronized up to terminal) | No |
Interrupts/diagnostics/status information |
Diagnostics function | No |
Substitute values connectable | Yes; 0/1 |
Diagnostics indication LED |
Status indicator digital output (green) | Yes |
Parameter |
Remark | 3 byte |
Response to CPU/master STOP | Substitute a value/keep last value |
Potential separation |
Potential separation digital outputs |
between the channels | Yes |
between the channels and backplane bus | Yes |
Between the channels and load voltage L+ | Yes |
Isolation |
tested with |
Channels against backplane bus and load voltage L+ | 1500 V AC |
Load voltage L+ against backplane bus | 500 V DC |
Ambient conditions |
Ambient temperature during operation |
min. | -25 °C; = Tmin |
max. | 70 °C; = Tmax |
Altitude during operation relating to sea level |
Installation altitude above sea level, max. | 2 000 m |
Ambient air temperature-barometric pressure-altitude | Tmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) |
Relative humidity |
With condensation, tested in accordance with IEC 60068-2-38, max. | 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) |
Resistance |
Use in stationary industrial systems |
— to biologically active substances according to EN 60721-3-3 | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request |
— to chemically active substances according to EN 60721-3-3 | Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); * |
— to mechanically active substances according to EN 60721-3-3 | Yes; Class 3S4 incl. sand, dust, * |
Use on ships/at sea |
— to biologically active substances according to EN 60721-3-6 | Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on request |
— to chemically active substances according to EN 60721-3-6 | Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); * |
— to mechanically active substances according to EN 60721-3-6 | Yes; Class 6S3 incl. sand, dust; * |
Remark |
— Note regarding classification of environmental conditions acc. to EN 60721 | * The supplied plug covers must remain in place over the unused interfaces during operation! |
Dimensions |
Width | 15 mm |
Height | 81 mm |
Depth | 52 mm |
Weights |
Weight, approx. | 50 g |
last modified: | 03/25/2019 |