| SIPLUS ET 200S EM 2AI Standard U -25...+60°C based on 6ES7134-4FB01-0AB0 |
Supply voltage |
Load voltage L+ |
Rated value (DC) | 24 V; From power module |
Reverse polarity protection | Yes |
Input current |
from load voltage L+ (without load), max. | 30 mA |
from backplane bus 3.3 V DC, max. | 10 mA |
Power loss |
Power loss, typ. | 0.6 W |
Address area |
Address space per module |
Address space per module, max. | 4 byte |
Analog inputs |
Number of analog inputs | 2 |
permissible input voltage for voltage input (destruction limit), max. | 35 V; 35 V continuous; 75 V for max. 1 ms (mark to space ratio 1:20) |
Cycle time (all channels) max. | Number of active channels per module x basic conversion time |
Input ranges (rated values), voltages |
1 V to 5 V | Yes |
-10 V to +10 V | Yes |
-5 V to +5 V | Yes |
Cable length |
shielded, max. | 200 m |
Analog value generation for the inputs |
Measurement principle | integrating |
Integration and conversion time/resolution per channel |
Resolution with overrange (bit including sign), max. | 14 bit; ±10 V: 13 bit + sign, ±5 V: 13 bit + sign; 1 to 5 V: 13 bit |
Integration time (ms) | 16,7 / 20 ms |
Interference voltage suppression for interference frequency f1 in Hz | 50 / 60 Hz |
Conversion time (per channel) | 65 ms; 55 / 65 ms |
Smoothing of measured values |
parameterizable | Yes; In four stages by means of digital filtering |
Step: None | Yes; 1x cycle time |
Step: low | Yes; 4x cycle time |
Step: Medium | Yes; 32x cycle time |
Step: High | Yes; 64x cycle time |
Errors/accuracies |
Linearity error (relative to input range), (+/-) | 0.01 % |
Temperature error (relative to input range), (+/-) | 0.01 %/K |
Crosstalk between the inputs, min. | -50 dB |
Repeat accuracy in steady state at 25 °C (relative to input range), (+/-) | 0.05 % |
Operational error limit in overall temperature range |
Voltage, relative to input range, (+/-) | 0.6 % |
Basic error limit (operational limit at 25 °C) |
Voltage, relative to input range, (+/-) | 0.4 % |
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency |
Series mode interference (peak value of interference < rated value of input range), min. | 70 dB |
Common mode interference (USS < 2.5 V) , min. | 90 dB |
Isochronous mode |
Isochronous operation (application synchronized up to terminal) | No |
Interrupts/diagnostics/status information |
Diagnostic messages |
Wire-break | Yes; Measuring range 1 to 5 V only |
Group error | Yes |
Overflow/underflow | Yes |
Diagnostics indication LED |
Group error SF (red) | Yes |
Parameter |
Remark | 4 byte |
Diagnostics wire break | Disable / enable (only in measuring range 1 to 5 V) |
Measurement type/range | deactivated / ±5 V / 1 to 5 V / ±10 V |
Group diagnostics | Disable / enable |
Overflow/underflow | Disable / enable |
Potential separation |
Potential separation analog inputs |
between the channels | No |
between the channels and backplane bus | Yes |
Between the channels and load voltage L+ | Yes |
Permissible potential difference |
Between the inputs and MANA (UCM) | 2 V AC PP |
between MANA and M internally (UISO) | 75 V DC/60 V AC |
Isolation |
Isolation tested with | 500 V DC |
Standards, approvals, certificates |
CE mark | Yes |
Ambient conditions |
Ambient temperature during operation |
min. | -25 °C; = Tmin |
max. | 70 °C; = Tmax |
Altitude during operation relating to sea level |
Installation altitude above sea level, max. | 5 000 m |
Ambient air temperature-barometric pressure-altitude | Tmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m) |
Relative humidity |
With condensation, tested in accordance with IEC 60068-2-38, max. | 100 %; incl. condensation / frost permitted (no commissioning under condensation conditions) |
Resistance |
Use in stationary industrial systems |
— to biologically active substances according to EN 60721-3-3 | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request |
— to chemically active substances according to EN 60721-3-3 | Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); * |
— to mechanically active substances according to EN 60721-3-3 | Yes; Class 3S4 incl. sand, dust, * |
Use on ships/at sea |
— to biologically active substances according to EN 60721-3-6 | Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on request |
— to chemically active substances according to EN 60721-3-6 | Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); * |
— to mechanically active substances according to EN 60721-3-6 | Yes; Class 6S3 incl. sand, dust; * |
Remark |
— Note regarding classification of environmental conditions acc. to EN 60721 | * The supplied plug covers must remain in place over the unused interfaces during operation! |
Dimensions |
Width | 15 mm |
Height | 81 mm |
Depth | 52 mm |
Weights |
Weight, approx. | 40 g |
last modified: | 03/13/2019 |