| ***Spare part*** SIPLUS ET 200S F-DO 24 V PROFIsafe -25...+60 °C with conformal coating based on 6ES7138-4FB03-0AB0 |
Supply voltage |
Load voltage L+ |
Rated value (DC) | 24 V |
Reverse polarity protection | No |
Input current |
From load voltage L+ (no load), typ. | 100 mA |
from backplane bus 3.3 V DC, max. | 28 mA |
Power loss |
Power loss, typ. | 3.5 W |
Digital outputs |
Number of digital outputs | 4 |
Short-circuit protection | Yes |
Limitation of inductive shutdown voltage to | Typ. (2L+) -47 V |
Controlling a digital input | No |
Switching capacity of the outputs |
on lamp load, max. | 10 W |
Load resistance range |
lower limit | 12 Ω |
upper limit | 1 kΩ |
Output voltage |
for signal "1", min. | L+ (-2,0 V), current sourcing switch: L+ (-1,5 V), voltage drop on current sinking switch: max. 0.5 V |
Output current |
for signal "1" rated value | 2 A |
for signal "1" permissible range, min. | 20 mA |
for signal "1" permissible range, max. | 2.4 A |
for signal "0" residual current, max. | 0.5 mA; Current-sourcing: max. 0.5 mA; Current sinking: max. 4 mA |
Parallel switching of two outputs |
for uprating | No |
for redundant control of a load | No |
Switching frequency |
with resistive load, max. | 30 Hz |
with inductive load, max. | 0.1 Hz |
on lamp load, max. | 10 Hz |
Total current of the outputs |
Current per module, max. | 6 A |
Total current of the outputs (per group) |
horizontal installation |
— up to 40 °C, max. | 6 A |
— up to 55 °C, max. | 5 A |
— up to 60 °C, max. | 4 A |
vertical installation |
— up to 40 °C, max. | 4 A |
Cable length |
shielded, max. | 200 m |
unshielded, max. | 200 m |
Interrupts/diagnostics/status information |
Diagnostics function | Yes |
Diagnostic messages |
Wire-break | Yes |
Short-circuit | Yes |
Diagnostics indication LED |
Group error SF (red) | Yes |
Status indicator digital output (green) | Yes |
Potential separation |
Potential separation digital outputs |
between the channels | No |
between the channels and backplane bus | Yes |
Between the channels and load voltage L+ | No |
Isolation |
Isolation tested with | 500 V DC |
tested with |
Channels against backplane bus and load voltage L+ | 1500 V AC |
Standards, approvals, certificates |
Highest safety class achievable in safety mode |
acc. to EN 954 | 4 |
Performance level according to ISO 13849-1 | e |
SIL acc. to IEC 61508 | SIL 3 |
Ambient conditions |
Ambient temperature during operation |
min. | -25 °C; = Tmin |
max. | 60 °C; = Tmax |
Altitude during operation relating to sea level |
Ambient air temperature-barometric pressure-altitude | Tmin ... Tmax at 1 080 hPa ... 795 hPa (-1 000 m ... +2 000 m) |
Relative humidity |
With condensation, tested in accordance with IEC 60068-2-38, max. | 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) |
Resistance |
Use in stationary industrial systems |
— to biologically active substances according to EN 60721-3-3 | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request |
— to chemically active substances according to EN 60721-3-3 | Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! |
— to mechanically active substances according to EN 60721-3-3 | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! |
Dimensions |
Width | 30 mm |
Height | 81 mm |
Depth | 52 mm |
Weights |
Weight, approx. | 85 g |
last modified: | 03/13/2019 |