| ***Spare part*** SIPLUS upmiter 4A -25...+70°C (S7-300 style) |
Supply voltage |
permissible range, lower limit (DC) | 10.5 V |
permissible range, upper limit (DC) | 59 V |
Input current |
Rated value at 24 V DC | 11 A; @ 10.5 V |
Rated value at 48 V DC | 1.8 A; @ 59 V |
Output voltage |
Rated value (DC) | 24 V |
Power up time, max. | 0.5 s |
Voltage rise time, typ. | 15 ms |
Short-circuit strength | Self-resetting PTC fuse |
Residual ripple, typ. | 100 mV |
Residual ripple, max. | 240 mV |
Output current |
Current output (rated value) | 4 A |
Power |
Active power input, typ. | 96 W; Not connectable in parallel for increased power |
Efficiency | 82 % |
Power loss |
Power loss, typ. | 15 W |
Interrupts/diagnostics/status information |
Diagnostics indication LED |
Output voltage 24 V DC (green) | Yes; OK for 24 V |
Potential separation |
primary/secondary | No |
EMC |
EMC interference immunity | EN 61000-6-2 |
EMC interference emission | EN 55022 Class A |
Degree and class of protection |
Degree of protection acc. to EN 60529 | IP20 |
Standards, approvals, certificates |
CE mark | Yes |
Railway application |
EN 50121-4 | No |
EN 50155 | No |
Ambient conditions |
Ambient temperature during operation |
min. | -25 °C; = Tmin |
max. | 70 °C; = Tmax |
Altitude during operation relating to sea level |
Ambient air temperature-barometric pressure-altitude | Tmin ... Tmax at 1 080 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax - 20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m) |
Relative humidity |
With condensation, tested in accordance with IEC 60068-2-38, max. | 100 %; RH incl. condensation/frost (no commissioning when condensation present), vertical mounting position |
Resistance |
Use in stationary industrial systems |
— to biologically active substances according to EN 60721-3-3 | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request |
— to chemically active substances according to EN 60721-3-3 | Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! |
— to mechanically active substances according to EN 60721-3-3 | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! |
Dimensions |
Width | 80 mm |
Height | 125 mm |
Depth | 120 mm |
Weights |
Weight, approx. | 0.75 kg |
last modified: | 03/13/2019 |